SPECIFICATIONS
1,999 or 9,999-Count Display Span
100 mV to 650 V Ranges
2 µA to 1 A Ranges
Special Scaling for 5 A Current Transformer
0.1 mV/Count Analog Output
Front-Panel Accessible Span Adjustment
Bright, 0.56" (14.2 mm) LED Display
Display Hold and Test
120/240 Vac, 9-32 Vdc Power
Screw-Terminal Barrier Strip
1/8 DIN Case
OPTIONS
Analog Output for User-Selected Span
Single-Setpoint 10 A Relay Control
Dual-Setpoint 10 A Relay Control
Parallel BCD Output, Isolated

The QUANTA® AC AVG voltmeter and ammeter use a precision op-amp rectifier circuit to provide an economical AC-average meter, which is calibrated to display the true-RMS value of sinusoidal signals. The QUANTA AC RMS voltmeter and ammeter use an integrated circuit that computes the true-root-mean-square value of complex waveforms. Screw-terminals are provided for AC or DC coupling. AC coupling allows the measurement of the AC component or ripple from a signal with both AC and DC components. DC coupling allows the measurement of true-RMS, including both DC and AC components.

The signal conditioner provides six current ranges, as determined by an internal shunt resistor. In addition, there is a special 5 A range, which allows direct connection to a current transformer (CT) with 5 A secondary, without need for a stepdown transformer. Proper scaling is obtained for primary currents of 10, 100 and 1000 A.

SPECIFICATIONS


ANALOG INPUT, Q2000C & Q2000F / Q3000C & Q3000F
Range
-
199.9 mV
1.999 V
Resolution
-
100 µV
1 mV
Maximum input
-
50 Vp
100 Vp
Input resistance
-
1.1 Mohm
1.1 Mohm

Range
19.99 V
199.9 V
650 V
Resolution
10 mV
100 mV
1 V
Maximum input
250 Vp
500 Vp
920 Vp
Input resistance
1.0 Mohm
1.0 Mohm
10 Mohm

ANALOG INPUT, Q2000D & Q2000G / Q3000D & Q3000G
Range
19.99 µA
199.9 µA
1.999 mA
Resolution
10 nA
100 nA
1 µA
Maximum input
3 mA
10 mA
30 mA
Input resistance
10 kohm
1 kohm
100ohm

Range
19.99 mA
199.9 mA
1.999 A
Resolution
10 µA
100 µA
1 mA
Maximum input
100 mA
500 mA
2.2 A
Input resistance
10 ohm
1 ohm
0.1 ohm

Range
19.99 A
199.9 A
1999 A
Resolution
10 mA
100 mA
1 A
Maximum input
5 A CT
5 A CT
5 A CT
Input resistance
0.01ohm
0.01ohm
0.01ohm

ANALOG INPUT, Q9000C & Q9000F / Q8000C & Q8000F
Range
99.99 mV
999.9 mV
Resolution
10 µV
100 µV
Maximum Input
50 Vp
100 Vp
Input Resistance
1.1 Mohm
1.1 Mohm

Range
9.999 V
99.99 V
650.V
Resolution
1 mV
10 mV
100 mV
Maximum Input
250 Vp
500 Vp
920 Vp
Input Resistance
1.0 Mohm
1.0 Mohm
10 Mohm

ANALOG INPUT, Q9000D & Q9000G / Q8000D & Q8000G
Range
9.999 µA
99.99 µA
999.9 µA
Resolution
1 nA
10 nA
100 nA
Maximum Input
3 mA
10 mA
30 mA
Input Resistance
10 kohm
1 kohm
100 ohm

Range
9.999 A
99.99 A
999.9 A
Resolution
1 mA
10 mA
100 mA
Maximum Input
5 A CT
5 A CT
5 A CT
Input Resistance
0.01 ohm
0.01 ohm
0.01 ohm

ACCURACY at 25°C (AC)
Maximum Error: ±0.1% of reading ±10 counts
Span tempco: ±0.01% of reading/°C (AC)
Step response: 1 s to 99.9% of span
Frequency range for rated accuracy:
147 to 1000 Hz
Warmup to rated accuracy: Less than 30 min.

ACCURACY at 25°C (RMS) (1% to 100% of full scale)

Maximum error, AC coupling:
±0.1% of reading ±10 cts, 47 Hz to 5 kHz
Maximum error, DC coupling: ±0.1% of reading ±10 cts, 9 Hz to 5 kH
Span tempco: ±0.03% of reading/°C (typ)
Zero tempco: 0.15 mV/°C (typ)
Step response: 1 sec to 99.9% of span
Warmup to rated accuracy: Less than 30 min.

CONVERSION
Technique:
Dual-slope, average-value
Signal integration period: 100 ms
Read rate: 2.5/sz


Range Code
Input Range
Range Code True RMS Q2000 / Q3000 Q9000 / Q8000
CVR2
FVR2
199.99 mV
99.99 mV
CVR3
FVR3
1.999 V
999.9 mV
CVR4
FVR4
19.99 V
9.999 V
CVR5
FVR5
199.9 V
99.99 V
CVR6
FVR6
650 V
650.0 V
DCR1
GCR1
19.99 µA
9.999 µA
DCR2
GCR2
199.9 µA
99.99 µA
DCR3
GCR3
1.999 mA
999.9 µA
DCR4
GCR4
19.99 mA
9.999 mA
DCR5
GCR5
199.99 mA
99.99 mA
DCR6
GCR6
1.999 A
999.9 mA
DCR7
GCR7
5 A CT
5 A CT

To Order ( * Complete Model No.) Prices Shown in U.S. Dollars
Q( * ) ( * ) ( * ) ( * )
POWER AND CASE
Price
2
- - - 3 1/2 digit standard case
$210
3
- - - 3 1/2 digit INFINITY® case
$240
8
- - - 4 digit INFINITY® case
$280
9
- - - 4 digit standard case
$250
- - - - POWER -
-
0
- - 120 Vac (49/440 Hz)
N/C
 
2
    240 Vac (49/440 Hz)
N/C
-
4
- - 9-32 Vdc (isolated)
$145
- - - - ANALOG OUTPUT -
- -
0
- ±1 or ±2 V non-isolated
N/C
- -
2
- 0-10 Vdc non-isolated
$70
- -
4
- Non-Isolated 4-20 mA
$70
- -
6
- Isolated 4-20 mA
$135
- - - - CONTROL OUTPUTS -
- - -
0
None
N/C
- - -
1
Dual-setpoint 10 A from “C” relay
$165
-    
4
Isolated BCD (5 V Logic)
$155
- - -
5
Single-setpoint 10 A from “C” relay
$125
- - - - CONTROL OUTPUTS -
- - -
*
AC AVG “Select Range Code”
$65
- - -
*
TRUE RMS “Select Range Code”
$100

Splash Proof Lens Cover
Model No.
Description
Price
SPC18
IP65/NEMA4 $30 with spring clamp
$30
SPC4
IP65/NEMA4 30 with screw clamp
$30

Copyright 2003, NEWPORT Electronics, Inc. All rights reserved.
NEWPORT Newport Home Products Purchase Quotes Pricelist Manuals Site Map Search e-mail Newport Home Products Purchase Quotes Pricelist Manuals Site Map Search e-mail Newport Home