MICROPROCESSOR-BASED
TEMPERATURE/ RELATIVE HUMIDITY RECORDER
The new Model CT485B completely self-contained Temperature/relative
humidity recorder is microprocessor based to accurately measure,
indicate and record temperature and relative humidity.
This rugged unit comes standard with alarms. They contain a single,
integral relay contact which closes in response to an alarm condition.
Simultaneous high and low alarm points for temperature and relative
humidity are user selectable. When the current conditions exceed
any of the preset values, the 2 Amp relay contact closes and an
audible alarm sounds. Flipping open a hinged front panel door
permits access to the power switch and controlling functions of
the recorder. The door comes with a locking mechanism. The user
may select 1, 7 or 32 day operation, program the instrument to
record in ºC or ºF, and access alarm and calibration
controls or max/min functions.
A separate 3-position switch next to the digital display selects
a ºC,ºF or %RH readout. The chart drive is stepper controlled
for precision, and a unique magnetic retaining knob eliminates
the possibility of paper tear.
Calibration of alarm models is digital, and a user may make calibration
adjustments in the field using the convenient panel pushbuttons.
An optional calibration lockout cover prevents unauthorized changing
of calibration codes. A stabilizing arm provides added stability
for benchtop use. The arm conveniently rotates under the unit
for wall mounting. Recessed rear mounting slots and a wall template
enable easy wall mounting. A decorative cover for the stabilizing
arm is supplied for wall mount use.
A standard 110 Vac power adaptor is supplied for continuous long-term
operation, along with four D-cell batteries for backup power or
field use. Each unit includes 6 feet of cable for remotely mounting
the sensor. A sensor holder clip is provided. Units come standard
with two chart light bulbs and a display back light. When using
the ac power adaptor, these bulbs provide easy viewing of the
chart and display in dimly lit conditions. A switch is provided
to allow the lights to be turned on or off.
SPECIFICATIONS
Measurement
Inputs: Temperature and humidity, with plug-in external sensor,
removable for remote location, 6' extension cable included; 0.02
to 1.20 Vdc signal with voltage input adaptor
TEMPERATURE
Range: -17 to 49ºC (2 to 120ºF)
Accuracy: ±1ºC
Sensor: Solid state
Response Time: 5 minutes for 63% step change
Display Resolution: 1ºC/1ºF
HUMIDITY
Range: 2 to 98% RH
Accuracy: ±3% @25ºC, between 20 and 90% of range (±5%
below 20% and above 90% @25°C)
Sensor: resistive polymer. Not recommended for use in corrosive
air environments
Response Time: 5 minutes for a 30 to 80% step change
Display Resolution: 1% RH 2 1/2 digit LCD, 0.5" high; low
battery
Display Modes: Front panel switchable between ºC,
ºF and %RH for continuous digital display; max/min storage
for both temperature and humidity or flashing to indicate alarm
condition
ELECTRONICS
Type: Microprocessor-controlled and linearized high and
low peak hold for both temperature and humidity, re-initializes
position at every chart change
CHART
Type: 8" circular, linear radial divisions; 1, 7 and 32
days, ºC and ºF scales
CHART DRIVE
Type: Stepper motor
Ranges: 1, 7 and 32 day, selectable
Accuracy: 1% of rotation
Chart Hold Down: magnetic hub lock
RECORDING PENS
Type: Disposable fiber tip, red for temperature, blue for
humidity
PEN DRIVES
Type: Motorized linear screw drive
Deadband: 1ºF, 1% RH
Zero: Automatic zero during chart change or power interruption
Penlift: Automatic on door opening; pens are door mounted
and swing clear of the chart when door opens
Pen Arms: Clear plastic to allow full chart viewing
OPERATING CONDITIONS (Recorder)
Temperature: 0 to 49ºC (32 to 120ºF)
Humidity: 0 to 90% RH, non-condensing
OPERATING CONDITIONS (Sensor
Remote)
(Sensors not recommended for use in a corrosive environment)
Temperature: -17 to 49ºC (2 to 120ºF)
Humidity: 0 to 98% RH
ALARMS
Alarms: User-selectable for high or low temperature and
humidity
Audible Alarm: Integral piezoelectric beeper
Alarm Relay Contacts: 1 Amp, 30 Vdc Normally open, single
pole, single throw (SPST)
Power (Recorder): Four D cells or 9Vdc/110, 50/60 Hz power
adaptor (supplied); 220 Vac power adaptor supplied where applicable
Battery Life: more than 1 month continuous operation in
32-day mode (average conditions)
Power Requirements: 300 mA "normal" during pen
movement for battery (dc) power; 500 mA "normal" during
pen movement for ac power using ac adaptor with chart lights on
(Note: the light bulbs drain 200 mA of current and the
display back light drains 20 mA)
DC Power Jack Voltage: 8.3 to 12.4 Vdc (nominal 9 Vdc),
1 Amp max.
MECHANICAL
Dimensions: 33.5 H x 27.1 W x 6.7 cm D (13 3/16" x 10 11/16"
x 2 5/8")
Weight: Approx. 3 Kg (7 lbs) including batteries
Mounting: "Keyhole" slots for wall mounting;
foot cover for benchtop use
Case: Rugged ABS plastic
ANALOG VOLTAGE INPUT ADAPTOR
Input: 20 mVdc to 1200 mVdc records as 2 to 120ºF,
input protection up to 20 Vdc or 10 Vac RMS
Input Impedance: 330 Kohms min.
Input Connections: Banana jacks, 19 mm (0.75") spacing
Cable Length: 305 mm (12")
|