 |
EIS-2B
- More info
- Web
Server and an Ethernet/Serial Bridge
-
Serves up to 32 devices
The
NEWPORT® EIS-2B "iServer"
is a DIN rail device which can connect up to thirty-two
(32) iDRX RS-485 instruments to an Ethernet network and
the Internet using standard TCP/IP protocol. It can also
be used as a simple Serial to Ethernet "bridge" or converter
to connect a single iDRN RS-232 device to an Ethernet network
and the Internet. (RS-232 Serial Communications are limited
to a single connection between two devices, such as one
computer and one signal conditioner. RS-485 is limited to
32 devices on a communications bus per hub or repeater.)
|
The "iServer" is a Web Server as well as an Ethernet-Serial
bridge and Hub for up to 32 RS-485 devices. The NEWPORT®
iServer is also compatible with the NEWPORT®
iSeries Controller and Meters, the INFINITY®
family of ultra high performance digital panel meters, and the
MICRO-INFINITY® series of Temperature and
Process controllers.
The "iServer" can also connect almost any RS-232
or RS-485 Serial Device to Ethernet. Each "iServer" is
assigned an IP address on the Ethernet network and can also be
assigned an easily remembered name. In fact, the device could
be assigned an authorized Internet IP address from an Internet
Service Provider and function as a World Wide Web Server delivering
whatever specific information is called for.
ETHERNET
and INTERNET
The iDRX signal conditioner can also be connected
to an Ethernet network using the EIS-2B module as
a Serial/Ethernet bridge. One EIS-2B module can be
a hub for up to 32 iDRX modules. The EIS-2B module
packages the ASCII serial communications in standard TCP/IP
Protocol for transmission over standard Ethernet networks
and the Internet. Unlike some manufacturer’s products this
system uses totally open, non-proprietary standards and
protocols for Ethernet and Internet. The user can integrate
these devices with any commercial or industrial grade networking
components that also comply with the popular international
standards. |
iDRN-PS-1000
- 24
Vdc Supply for iDRN/iDRX Modules
-
iDRN-PS -1000 Switching Supply Powers up to 7 Units
|
|
To
Order (Specify Model No.)
Prices Shown in U.S. Dollars
|
Model
|
Description
|
Price
|
|
|
Embedded
Internet Server, serves 32 devices |
$195
|
|
iDRN-PS-1000
|
Switching
Power supply, 95-240 Vac input, 24 Vdc output @850mA (power
7 units) |
$150
|
Software
|
Model
|
Description
|
Price
|
|
|
OPC
Server Software License |
$295
|
|
|
Active
X Controls and Configuration Software/iDRX Windows 95/98/NT.
Free Sample Visual Basic App Source Code. |
FREE
|
|
|
Active
X Controls and Configuration Software/iDRN Windows 95/98/NT.
Free Sample Visual Basic App Source Code. |
FREE
|
|
-FS
|
Factory
setup and scaling |
FREE
|
Accessories
|
Model
|
Description
|
Price
|
|
CAT-285
|
Bi-directional
RS-232-R3-485 converter for DRX series |
$148
|
|
DB9-RJ12
|
DB9
to RJ12 Connector Adapter, includes 7ft. RJ12 cord |
$30
|
|
DB25-RJ12
|
DB25
to RJ12 Connector Adapter, includes 7ft. RJ12 cord |
$30
|
|
RJ12T
|
RJ12“T”
Split Connector for RS-485 instruments, includes 7 ft. RJ12
cord |
$15
|
iDRX
Modules on RS485 Serial Bus
 |
Digital Output iDRX Modules
Connected to Ethernet
 |
|
Input
|
Process
|
Strain/Bridge
|
Thermocouple
|
RTD
|
|
Model
|
iDRN/iDRX-PR
|
iDRN/iDRX-ST
|
iDRN/iDRX-TC
|
iDRN/iDRX-RTD
|
|
Input
Type
|
dc
Millivolt, Millivolt Volt and Current
|
Millivolt
|
Thermocouple
Temperature sensor
|
RTD
Temperature sensor Pt100, 500, 1000 ohm
|
|
Input
Range
|
Full Scale Range: ±400 mV to ±10 V 0 0 to 20 mA
|
0
to 30 mV
0 to 100 mV
±100 m
|
J, K, T, E, R, S, B, N, J DIN
thermocouple full range
|
a
= 385, 392
Full range of RTD
2, 3 or 4-wire
|
|
Accuracy
|
0.1%
FS
|
0.2%
FS
|
±1°C
|
±0.5°C
|
|
Resolution
|
12
to 15 Bit
|
13
to 15 Bit
|
0.1°C
|
0.1°C
|
|
Output
|
iDRN Output: 0 to 10 V @ 10 mA max; 0 to 20 mA or 4 to
20 mA
iDRX Output: 2-wire (half duplex) RS-485
|
|
Excitation
|
14 Vdc @ 25 mA
|
10 V @ 30 mA
|
N/A
|
N/A
|
|
Input
|
Frequency
Pulse
|
ac
Voltage
|
ac
Current
|
|
Model
|
iDRN
/ iDRX-FP
|
iDRN
/ iDRX-ACV
|
iDRN
/ iDRX-ACC
|
|
Input
Type
|
NAMUR
Contact closure low level open collector
|
ac
Voltage
|
ac
Current
|
|
Input
Range
|
Full Scale Range:
20K to 200 M pulses /
0.2Hz to 50 KHz
|
Full
Scale Range:
400 mV to 400 V
|
Full
Scale Range:
10 mA to 5 A
|
|
Accuracy
|
0.1%
FS
|
0.2%
|
0.2%
|
|
Resolution
|
5
to 19 Bit
|
10
to 14 Bit
|
10
to 14 Bit
|
|
Output
|
iDRN Output: 0 to 10 V @ 10 mA max; 0 to 20 mA or 4 to 20
mA
iDRX Output: 2-wire (half duplex) RS-485 |
|
Excitation
|
5,
8.2 and 12.5 Vdc @ 25 mA
|
N/A
|
N/A
|
|