This is a 2-wire, 4-20 mA Current Transmitter
that accepts signals from 350, 500, 1K, 2.5K and 5K ohm bridges
and provides the amplification and common-mode rejection necessary
to control the current drawn from a 8 to 40 Vdc source to produce
the 4-20 mA output signal. The transmitter is designed for 0.5 to
4.0 mV/V bridge sensitivities. The transmitter does not provide
isolation between its input and the 4-20 mA output. It has two internal
reference voltages for powering the bridge. The 1.24 volt reference
is used with 1K ohm and lower resistance bridges. The 2.5 volt reference
is used with 2.5K and 5K ohm bridges.
SPECIFICATIONS
Input Span: User Selectable, 0.5 mV/V to 4 mV/V
Input Impedance: > or = to 10 Mohm
Output Span: 4 to 20 mA
Min. Output Current: 3.75 mA typical
Max. Output Current: 22 mA typical
Supply Voltage Range: 8 to 40 Vdc
Transducer Excitation: Selectable, 1.24 Vdc or 2.5 Vdc
Zero & Span Adjustability: 10% of any selected range
Accuracy: (includes linearity, hysteresis, stability) 0.5%
of any adjusted span
Repeatability: 0.05% of span
Response Time: 200 ms typical
Stability: Zero: within 0.02% of span/°C or 5 µA, whichever
is greater. Span: within 0.01% of span/°C
Max. Leadwire Resistance Effect: Less than 0.25 µV per ohm
Maximum Change-In-Supply Voltage Effect: 0.05% of span over
supply range
Output Ripple: Less than 0.05% of span, rms
Operating Temperature Range: -45 to 85°C (-49 to 185°F)