The NEWPORT® i8DH and i8DV
are high-quality, highly accurate
single loop autotune PID temperature
and process controllers for 1/8 DIN
(92 x 45 mm) horizontal or vertical
panel cutouts. Both devices feature
the same state-of-the-art technology,
uncompromising accuracy, and
quality backed by an extended
5-year warranty.
The i8DH and i8DV are
simple to configure and use, while
providing tremendous versatility and
a wealth of powerful features.
The i8DH and i8DV come
standard with your choice of
2 control or alarm outputs in almost
any combination: solid state relays
rated at 0.5 A @ 120/240 Vac;
Form "C" SPDT relays rated at
3 A @ 120/240 Vac; pulsed 10 Vdc
output for use with an external SSR;
or analog output (0 to 10 Vdc or
0 to 20 mA) selectable for control or
retransmission of the process value.
The universal temperature and
process instrument (i8 models)
offer a selection of 10 thermocouple
types as well as 2-, 3- or 4-wire
RTDs, process voltage and current.
The i8DH and i8DV are ideal
controllers for use with transmitters
and amplified transducers. Built-in
excitation is standard (24 Vdc
@ 25 mA). The units handle
0 to 20 mA process current and
process voltage in 3 scales:
0 to 100 mV, 0 to 1V, and 0 to 10V.
As with all iSeries devices, the process
value display can be programmed
to change color between GREEN, AMBER, or RED at any setpoint
or alarm point. The LEDs displaying
the process value on the i8DH
(horizontal 1/8 DIN) are the largest
digits of any 1/8 DIN controller.
The strain/process instrument
(model iS) meters and controllers
measure inputs from load cells,
pressure transducers, and most any
strain gage sensor. Input ranges
include 0 to 100 mVdc; -100 mVdc
to 1 Vdc; 0 to 10 Vdc in addition to
0 to 20 mA. Excitation for transducers
of 5 V and 10 V is standard.
The highly recommended networking
and communications options include
direct Ethernet LAN connectivity
with an embedded Web server, and
serial communications. The C24
serial communications option
includes both RS232 and RS485
which can be selected from the
menu as well as both a
straightforward ASCII protocol or
MODBUS®. The C4EIT option
includes both Ethernet and RS485
ASCII/MODBUS on 1 device.
The iSeries, with the network
options, are designed for easy
integration with popular industrial
automation and control programs
as well as Microsoft Visual Basic
and Excel. Newport® provides
free configuration software which
makes it fast and easy to get up
and running with many applications.
Available for download off the Internet.
For more information on iSeries click here
|
|
|
|
|
† All dollar amounts on this site are shown in US currency.
Note: Comes with complete operator’s manual.
1. "-DC", "-C24", and "-C4EIT" not available with excitation. 2. Analog output is not available with "-AL" units. 3. "-SM" option not available on iS strain models.
Ordering Example: (1) i8DH43 horizontal 1/8 DIN dual display with pulse control and relay, (1) i8DV53 1/8 DIN dual display vertical controller with analogue output and relay, (1) iS8DH22 1/8 DIN dual display horizontal controller with 2 SSR outputs = $1110
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
Part Number Builder |
 |
 |
 |
 |
 |
 |
|
|
|
Option Descriptions
|
|
(1)
|
Input Type
|
| |
Select i8 for Standard 1/8 DIN Meter i8C for Compact case (note - Isolated Analog and Ethernet options are not available in the compact case) i8A for Isolated linear analog output (note - Analog output (option 5) and Ethernet options are not available for this i8A controller) i8DH for 1/8 DIN Meter Dual Display Horizontal i8DV for 1/8 DIN Meter Dual Display Vertical iS8 for 1/8 DIN Strain Meter
|
(2)
|
Control Outputs
|
| |
Select 00 for No Output 22 for Two Solid State Relays 23 for One Solid State Relay - Form C SPDT 24 for 1 SSR for Pulse 10V dc 33 for 2 Relays - Form C SPDT 42 for Pulsed 10 V dc and SSR Relay 43 for Pulsed 10 V dc and Form C Relay 44 for 2 pulsed 10 V dc 52 for Analog Output and SSR 53 for Analog output and Relay 54 for Analog output and pulse
|
(3)
|
Network Options
|
| |
Select Nothing(leave field blank) for No network option -C24 for Isolated RS232 and RS485/422 300 to 19.2 k baud -EIT for Ethernet w/ Embedded Web Server (not available for compact case) -C4EIT for Ethernet w/ Embedded Web Server + Isolated RS485/422 (not available for compact case)
|
(4)
|
Power Supply
|
| |
Select Nothing(leave field blank) for Standard power input for 90 to 240 Vac/dc, 50 to 400 Hz -DC for 12-36 Vdc, 24 Vac for Single Display, 20-36 Vdc for Dual Display (Internal Excitation is not available with this option)
|
(5)
|
Menu Options
|
| |
Select Nothing(leave field blank) for no option -AL for for Limit Alarm Version (Alarm Menu, No PID Control) -SM for for Simplified Menu Version (ON/OFF Control, No PID Control)
|
(6)
|
Factory Setup
|
| |
Select Nothing(leave field blank) for no option ,FS for Factory Setup and Configuration
|
| NOTE: All combinations may not be valid, check spec sheet for valid part numbers. |
| | | | |
|
 |
 |
|
|
|
|
Keywords: i-Series 1/8 DIN Programmable Temperature, Strain / Process Controllers, with RS-232 RS-485 Communication, controller, PID temperature controller, tehrmocouple controller, digital PID Controllers, digital controller, digital indicator, digital panel meter, embedded web server, p & id, process instrumentation, heater controller, process meter, p&id, thermocouple controller
|
Back to top |
|
|