Navigation image map
Contact Us Distributor Site Map Manuals Home Products


INFINITY® Rate / Total / Batch Meters
INF7

INFINITY® Rate / Total / Batch Meters
Rate and Total Simultaneously
Batch Controller
Real-Time Clock
Square Root Programmable
Isolated BCD Option
Isolated Analog Input Option
5 Open Collector Outputs Standard



Electromagnetic Compatibility


The INF7 is the ultimate 6-digit multi-functional process indicator/ controller. Each unit can be easily configured via the front-panel pushbuttons or optional serial communication boards, to be used as a ratemeter/totalizer, batch controller, or real-time clock. Rate may be displayed in engineering units. In addition, average rate, which is a running average that works like a filter, is selectable to help eliminate noise, yet does not introduce a long delay for a step change in the input frequency response. With the optional analog input board, the INF7 can be configured to accept a signal, such as 4-20 mA dc, from any typical differential flow transmitter and extract the square root of this signal, providing a linear display in any engineering units desired. The INF7 can also be programmed as a single input batch controller. It can simultaneously count the batch, number of batches completed, and the grand total of pulses received. In addition, it has an internal timer for process time measurement displayed in HH MM SS format.

RATE METER/TOTALIZER ("R")
The INF7 can be configured, via the front-panel pushbuttons and/or through the optional serial communications boards, to display rate in engineering units. In addition, average rate, which is a running average that works like a filter, is selectable to help eliminate noise, yet does not introduce a long delay for step change in the frequency input response. Gate times (averaging times) of 0.03, 0.1 and 3.0 seconds are software selectable. Calculations for gate times are done concurrently with averaging and as a result, any change in input frequency, even for a short duration, will be captured. In the rate mode, total can also be scaled in engineering units via a separate scale and offset and can be different from the engineering units selected for rate. Process time can also be selected and displayed HH:MM:SS format. When the optional analog to frequency input board is selected, the INF7 will accept 0-5V dc, 1-5 Vdc, 0-10 Vdc, 0-20 mA dc, and 4-20 mA dc inputs allowing the INF7 to operate as an Integrating Totalizer and Rate meter. This allows the user to display and control in linear flow applications. Because of the enhanced capabilities of the INF7, upon loss of power, grand total and the process time are stored into the non-volatile memory and restored with power-on without the need for battery back-up

RATE METER/TOTALIZER with INTEGRAL SQUARE ROOT EXTRACTOR ("Q")
When the optional analog input board is ordered, the INF7 can be configured to accept a signal, such as 4-20 mA dc, from any typical differential flow transmitter, and extract the square root of this signal providing a linear display in any engineering units desired. The rate is first measured and then the square root is digitally calculated insuring an accurate reading. By also adding the optional analog output board, the INF7 becomes an extremely affordable indicating totalizer and flow transmitter. Include the optional dual-relay output board and ON/OFF control is added. Now add an optional serial input/output board and the INF7 becomes a smart transmitter. The possibilities are endless.

BATCH CONTROLLER ("B")
The INF7 can also be programmed as a single input batch controller. It can simultaneously count the batch, number of batches completed, and the grand total of pulses received. In addition, it has an internal timer for process time measurement displayed in HH:MM:SS format. Any of the above mentioned functions may easily be displayed by pushing the front-panel pushbutton labeled display, without stopping the process. The batch counter can easily be programmed to count up from zero or down from a programmed preset. A batch, reset, at any time, starts the batch from the beginning and adds one count to the total number of batches. Resetting the batch controller can be automatic and the grand total is not affected. The number of times the batch can be repeated is also programmable up to 1 million. Because of the enhanced capabilities of the INF7, upon loss of power, batch, number of batches, grand total, and process time are stored into the non-volatile memory and restored with power.

CLOCK ("C")
The INF7 can be configured as a real time, 12, 24 or 100-hour clock, which displays in HH:MM:SS format. The time base is derived from the power line frequency, 50 or 60 Hz, which insures the accuracy. In addition, one open-collector output is standard for this mode and can be used for either alarm or control. Infinite capabilities are available for the end user with the addition of any one, or a combination, of the optional control or BCD outputs, analog output, or serial communication boards. Because of the modular design, the output boards can easily be installed, even at a later date, just in case your application needs change.

SPECIFICATIONS
Power: 115 or 230 Vac, ±10%
Power Consumption: 6 W nominal, 12.5 W max.
Accuracy: 0.001% of reading ±1 LSD, ± trigger error
Power Consumption: 6 W nominal, 12.5 W max.
Case Material: 94V-0 UL-rated polycarbonate
Battery Backup: For internal clock; requires external 6 to 12Vdc @ 50mA

SIGNAL CONDITIONERS
Non-isolated TTL-level pulse input standard
Threshold: 0.7 to 2.0 V
Frequency Ranges: 0.2 Hz to 20 kHz
Protection Level: 24 V
Trigger Slope: Positive
Input resistance: 30 k ohm pull-up resistor to +5 Vdc
Connection (TTL): Plug-in screw terminal
Contact Closure Connection: plug-in screw terminal
Debounce Filter: R/C filter, 20ms 8Hz corner, jumper selectable
NPN Open Collector Connection: plug-in screw terminal
Sensor Excitation (NPN): 16-30 V @ 70 mA non-regulated

ISOLATED PULSE INPUT WITH EXCITATION
(Voltage input and passive magnetic pickup; most popular)
Connection: plug-in screw terminal
Sensitivity: 20 mV rms
Maximum Signal: 60 V rms with protection to 240 V
Input Impedance: 75 k ohm min
Hysteresis: 50 mV
Threshold: Zero crossing or positive offset, jumper selectable

NPN OPEN-COLLECTOR INPUT
Connection: plug-in screw terminal
Sensor Excitation: 5, 8, or 12 V dc regulated
Pull-up: Internal 1k ohm

NAMUR INPUT
Connection: plug-in screw terminal
Sensor Excitation: 8.2 V
Internal Load/Source Impedance: 1 kOhm
Activated: <1 mA
Deactivated: >3 mA

CONTACT-CLOSURE INPUT
Connection: plug-in screw terminal
Sensor Excitation: 5, 8, or 12 V regulated
Pull-up: Internal 1k ohm
Debounce Filter: R/C filter, 20ms 8Hz corner, jumper selectable
Frequency Range: 10 on/off per second

ISOLATED ANALOG INPUT (optional)
Method: Linear Analog to frequency converter
Connection: plug-in screw terminal
Input Resistance: 25 ohms for 4-20 mA input, 500 ohms for 0-1mA input,
and 100 k ohm for voltage input.
Sensor Excitation: 24V dc @ 25 mA
Signal Range(s): 0-5 Vdc, 1-5 Vdc, 0-10 Vdc, 0-1 mA dc, 4-20 mA dc
Output Range: 0 to 0.77Hz, 0 to 100Hz, 0 to 6.4 kHz, jumper selected.
Isolation: SIG GND to DIG GND: 354 Vp
Low-Level Shutoff: programmable
Non-Linearity Max.: 0.02% FS
Accuracy at 25°C: 0.05% FS
Temperature Coefficient: 50 ppm/°C

NMR: 60dB @ 60Hz, 57dB @ 50 Hz
Step Response: 10 to 90% full-scale, 50 msec
Turndown Ratio: max. offset divided by minimum span, 1000 with 0.1% resolution; 100 with 0.01% resolution

CONTROL AND ALARM OUTPUTS
(Main Board)
Setpoint output:
Five, isolated open-collector transistors, On = 150 mA dc @1 V sink, Off = 30V dc max.

ISOLATED PARALLEL BCD "OPTION"
BCD type: Isolated, stored, buffered, addressable, tri-state
Digit Addressing: 3 or 6-digit at a time
Output level: 5 V dc TTL/CMOS compatible, 10 LSTTL loads
Power: External 5 V dc for isolated BCD, Internal 5 V dc for non-isolated BCD

DUAL RELAY BOARD "OPTION"
Output type: Dual 7 A, SPDT form "C" relays

QUAD RELAY BOARD "OPTION"
Output type: Dual 7 A, and Dual 1A SPDT form "C" relays

ANALOG OUTPUT BOARD "OPTION"
Output level: 0-10 V dc. 0-20 mA dc, or 4-20 mA dc
Compliance: 12 V dc or 20 mA max.
Accuracy at 25°C: 0.05% FS
Isolation: 354 Vp per IEC spacing Signal Ground to Analog Return
Resolution: 15 Bits
Step Response: 50 ms
Zero and span adjust: 2-point XY coordinate
Turndown ratio: 1000 with 0.1% resolution
Max. offset – min. span: 100 with 0.01% resolution

DATA OUTPUT "OPTIONS"
RS-232
Connection:
RJ-12, 6-wire telephone jack
Baud rate(s): 300, 1200, 2400, 9600 and 19200
Format: 7 bit ASCII
Parity: None, Odd, or Even
Stop bits: One, or Two
Handshake: Message or Character if in continuous, Xon Xoff for Command mode
Print Request: May be programmed to send one ASCII message for contact closure at rear connector.
Isolation: 354 Vp per IEC spacing Signal Ground to Analog Return

RS-485
Connection: RJ-12, 6-wire telephone jack
Baud rate(s): 300, 1200, 2400, 9600 and 19200
Format: 7 bit ASCII
Parity: None, Odd, or Even
Stop bits: One, or Two
Handshake: Xon Xoff , Half Duplex
Address: 0 (Common address), 1 to 199.
Modes: Alarm and normal
Isolation: 354 Vp per IEC spacing Signal Ground to Analog Return


Product Selection (Specify Model Number, see variations below in partnumber builder table)
 Part Number   Availability   Price    Description   
 INF7-02000-R in-stock    $650.00     Rate Meter/Totalizer/Batch Meter with 115 V ac power and green LED display, analog input (isolated) w/excitation, 5 open-collector transistors, operating mode set to rate totalize  
 INF7-01010-R in-stock    $640.00     Rate Meter/Totalizer/Batch Meter with 115 V ac power and green LED display, isolated pulse input with excitation, 5 open-collector transistors, Isolated analog output, operating mode set to rate totalize  
 INF7-00010-R in-stock    $565.00     Rate Meter/Totalizer/Batch Meter with 115 V ac power and green LED display, TTL input 5V logic, 5 open-collector transistors, Isolated analog output, operating mode set to rate totalize  
 INF7-01200-R in-stock    $605.00     Rate Meter/Totalizer/Batch Meter with 115 V ac power and green LED display, isolated pulse input with excitation, dual 7A SPDT relays, operating mode set to rate totalize  
 Accessories
 9SC2 in-stock    $31.50     9-pin serial connector for RS-232  
 9SC4 in-stock    $31.50     9-pin serial connector for RS-485  
 25SC2 in-stock    $31.50     25-pin serial connector for RS-232  
 25SC4 in-stock    $31.50     25-pin serial connector for RS-485  
 
All dollar amounts on this site are shown in US currency.

 Part Number Builder
(1) (2) (3) (4) (5) (6) (7)
I
I
N
N
F
F
7
7
-
-
Option Descriptions
(1) POWER AND LED COLOR
  Select
0 for Designates 115 V ac power and red LED display
1 for Designates 230 V ac power and red LED display
2 for Designates 115 V ac power and green LED display
3 for Designates 230 V ac power and green LED display
(2) INPUT(S)
  Select
0 for Non-isolated inputs
1 for Isolated input (P7A1)
2 for Isolated Analog to Frequency converter input (P7A5A)
(3) BCD AND CONTROL OUTPUT(S)
  Select
0 for Five optically isolated open-collector outputs
1 for Isolated parallel BCD output (BCD1)
2 for Isolated dual 7 A relays (REL1)
3 for Isolated dual 7 amp and dual 1 amp relays (REL4)
(4) ANALOG OUTPUT
  Select
0 for No analog output
1 for Isolated analog output (ANO3-INF7)
(5) SERIAL OUTPUTS
  Select
0 for No serial output
1 for Isolated RS-232 serial output (RS24)
2 for Isolated RS-485 serial addressable output (RS24)
(6) OPERATING MODES - Factory default setup is for standard rate/totalizer
  Select
-R for Rate totalize (factory default setting)
-Q for Rate/totalize with integral square root extraction
-B for Batch controller
-C for Clock
(7) ADD-ON OPTION
  Select
Nothing(leave field blank) for No Options
,BL for Blank lens
 NOTE: All combinations may not be valid, check spec sheet for valid part numbers.


   
Keywords: INFINITY® Rate / Total / Batch Meters