| OPTIONS |
 |
Isolated
Dual 7 Amp Form C Relays |
 |
Isolated
Parallel BCD Output |
 |
Isolated
Analog Output of 0-10 Vdc, 0-5 Vdc, 1-5 Vdc, 0-20 mA dc and
4-20 mA dc |
 |
Isolated
Serial RS-232 |
 |
Isolated
RS-485, Addressable up to 199 Units |
Four standard setpoints give you the flexibility to control or alarm
your system completely. The meter lets you scale and offset the input
signal into any engineering units desired, plus select a two-point
data method of scale and offset that eliminates the signal errors
transmitted from a sensor.
You can capture and display both peak and valley levels of your input
signals, an important feature for such applications as destructive
and pressure testing. Five different kinds of excitation are available
for sensors such as transmitters (24 Vdc @ 25 mA), strain gages (1.5
to 10 Vdc @ up to 60 mA max.), slide-wire potentiometers (1.25 Vdc
@ 30 mA).
The meter is delivered configured for the input type you choose. The
meter can be easily reconfigured using the front pushbuttons or via
either of the optional serial communications boards. All options are
field installable, so you easily upgrade as your needs change.
COMMON
SPECIFICATIONS FOR INFINITY®
METERS
Accuracy:
±0.005% rdg
Span Temperature Coefficient: ±20 ppm
Step Response: 1 sec to 99.9%
Warmup to Rated Accuracy: 50 min
Operating Ambient: 0 to 50°C (32 to 122°F), 95%RH, non-condensing
Storage Ambient: -40 to 85°C (-40 to 185°F)
Power: 115 or 230 Vac, 49-400 Hz; 10 to 32 Vdc
Power Consumption: 6 W nominal, 10 W max.
Normal Mode Rejection: 60 dB
Common Mode Rejection: 120 dB
Common Mode Voltage: 1500 V peak per Hv test
Resolution: 15-bit
Conversion: dual-slope technique
Reading Rate: 3/sec or 13/sec, 60 Hz; 3/sec or 12/sec, 50 Hz
Display: red or green 6-digit, 14-segment, 13.7 mm (0.54");
4 alarm indicators
Dimensions: 48 H x 96 W x 165 D mm (1.89" x 3.78" x 6.5")
Panel Cutout: 45 H x 92 W mm (1.772" x 3.622"); 1/8 DIN
Weight: 574 g (1.27 lb)
TTL Outputs: four, isolated open collector; rated 150 mA at
1 V sink, 30 V open
Dual Relays: form C, 7 A at 30 Vdc or 230 Vac
BCD Output: isolated, tri-state, TTL/CMOS compatible; external
5 V supply for isolated; internal 5 V supply for non-isolated
Four Relay Option: dual 7A relays and dual 1 A relays
Analog Output: 0-5 V/1-5 V/0-10 V/0-20 mA/4-20 mA, user selectable;
354 Vp isolation; 14-bit resolution; 0.1% accuracy, 50 msec step response
RS-232 Communications: 300/600/1200/2400/4800/9600/19.2k baud;
RJ11 4-wire connection; complete program setup and message display
capability; programmable to transmit current display, alarm status,
min/max, actual measured input value and status
RS-485 Communications: 300/600/1200/2400/4800/9600/19.2k baud;
RJ12 6-wire connection; addressable from 0 to 199
Voltage Input Ranges: 0-100 mV, 0-1 V, 0-5 V, 1-5 V, 0-10 V,
0-100 V, ±50 mV, ±500 mV, ±5 V, ±50 V
Current Input Ranges: 0-20 mA, 4-20 mA
Input Configuration: single-ended
Polarity: unipolar/bipolar, programmable
Span Adjustment: +0.00001 to 500,000, programmable
Offset Adjustment: 0 to 999,999 or 0 to -99,999, programmable
Sensor Excitation: 24 V at 25 mA for loop power
|
|
|
† All dollar amounts on this site are shown in US currency.
Ordering Example: (1) INFP-0001-C2 INFINITY® Process Panel Meter, 115 Vac power, red LED display, open collector outputs, isolated RS-232 output, 4-20 mA input = $655
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
Part Number Builder |
 |
 |
 |
 |
 |
 |
|
|
|
Option Descriptions
|
|
(1)
|
Basic Model
|
| |
Select INFP for INFINITY® Process Panel Meter INFZP for Split meter with remote display
|
(2)
|
Power and Display
|
| |
Select 0 for 115 Vac power with red LED display 1 for 230 Vac power with red LED display 2 for 115 Vac power with green LED display 3 for 230 Vac power with green LED display 4 for 10 to 32 Vdc power with red LED display 5 for 10 to 32 Vdc power with green LED display
|
(3)
|
Control Output
|
| |
Select 0 for four NPN open collector transistors 1 for isolated parallel BCD 2 for two 7 A relays 3 for two 7 A relays and two 1 A relays (not available with 10 to 32 Vdc power option)
|
(4)
|
Analog Output
|
| |
Select 0 for no analog output 1 for isolated analog output
|
(5)
|
Serial Output
|
| |
Select 0 for no serial output 1 for isolated RS-232 2 for isolated RS-485
|
(6)
|
Input Type and Range
|
| |
Select DC1 for 0 to 100 mVdc DC2 for 0 to 1 Vdc DC3 for 0 to 5 Vdc DC4 for 1 to 5 Vdc DC5 for 0 to 10 Vdc DC6 for 0 to 100 Vdc DC7 for ±50 mVdc DC8 for ±500 mVdc DC9 for ±5 Vdc DC10 for ±50 Vdc C1 for 0 to 20 mA C2 for 4 to 20 mA
|
| NOTE: All combinations may not be valid, check spec sheet for valid part numbers. |
| | | | |
|
 |
 |
|
|
|
|
Back to top |
|
|