Navigation image map
Home Products Quotes Price List Manuals Site Map View Cart Contact Us


iTH Series

from $390


Humidity + Temperature Controllers





iSeries Family - Selection Guide

Dual Loop Control
iSERIES MANUALS/CONFIGURATION SOFTWARE
•  MANUALS iTH Controller & Quickstarts
•  MANUALS iSeries Communication Manual
•  MANUALS iSeries Embedded Ethernet Manual
•  SOFTWARE OPC Server
•  SOFTWARE MAIL NOTIFIER w/ HTTPget & SetIP (for Ethernet option)
•  SOFTWARE iCONNECT (for Ethernet option)
•  SPECS - PDF
•  PRICE
•  CALIBRATION
•  MECHANICAL SPECS & CAD FILES
  REQUIRES ADOBE ACROBAT - HELP
Humidity + Temperature
High Accuracy ±0.5°C and ±2% RH
4 Popular DIN Sizes
Ethernet and Serial Communications (optional)
User-friendly, Simple to Configure
Full Autotune PID Control
2 Control or Alarm Outputs (optional)
Choice of Relays, SSR, DC Pulse, Analog Voltage and Current
Made in Santa Ana, CA
Electromagnetic Compatibility
Programmable Ramp and Soak for Humidity and/or Temperature
RH/Temperature Probe included

The NEWPORT® iTH Series instruments monitor and control both temperature and relative humidity.

All meters and controllers in the series are high quality, highly accurate instruments featuring Newport's award-winning iSeries technology, uncompromising accuracy, and Made in the U.S.A. quality, backed by an extended 5-year warranty.

The instruments are simple to configure and use, while providing tremendous versatility and a wealth of powerful features. The NEWPORT iTH Series instruments are available either as monitors or controllers. The monitors are extremely accurate programmable digital panel meters displaying humidity, temperature, or dew point. The controllers also provide dual loop control for both humidity and temperature and are easily programmed for any control or alarming requirement from simple on-off to full autotune PID control.

The iTH family of meters and controllers are available in four true DIN sizes: the ultra compact 1/32 DIN (the world's smallest dual loop Humidity + Temperature controller); the popular midsize 1/16 DIN square bezel with dual display; the 1/8 DIN vertical, and the 1/8 DIN horizontal with the big bright 21mm digits.

The NEWPORT iTH series LED displays can be programmed to change color between Green, Amber, and Red at any set point or alarm point.

The iTH controller models offer a choice of two control or alarm outputs in almost any combination: solid state relays (SSR); Form "C" SPDT (Single Pole Double Throw) relays; pulsed 10 Vdc output for use with an external SSR; or Analog Out
put selectable for control or retransmission of the process value.

The Networking and Communications options (highly recommended) include direct Ethernet LAN connectivity with an Embedded Web Server, and serial communications. The -C24 serial communications option includes both RS-232 and RS-485. Protocols include both MODBUS and a straightforward ASCII protocol. The -C4EI option includes both Ethernet and RS-485 ASCII/MODBUS on one device.

The iTH Series meters and controllers are designed for easy integration with popular industrial automation, data acquisition and control programs as well as Microsoft Visual Basic and Excel. NEWPORT® provides free configuration and data acquisition software and demos which makes it fast and easy to get up and running with many applications.

SPECIFICATIONS
Sensor Specifications
Relative Humidity Accuracy/Range:
±2% for 10 to 90% RH;
±3% for 0 to 10% RH & 90 to 100% RH
Non-linearity: ±3%
Hysteresis: ±1% RH
Response Time: 4 seconds (63% slowly moving air)
Repeatability: ±0.1%
Resolution: 0.03%, 12 bit

Temperature Accuracy/Range*:

±0.5°C (±1°F) for 0 to 80°C (32 to 176°F)
±1°C (±2°F) for -40 to 0°C and 80 to 124°C
(-40 to 32°F and 176 to 254°F)
Response Time: 5 seconds (63% slowly moving air)
Repeatability: ±0.1°C
Resolution: 0.01°C, 14 bit
*Note: extended temperature range is for Industrial Probe only, the controller's operating temp. is 0 to 50 °C.

 

Dimensions:
Industrial Probe iTHP-5, iTHP-2:
137mm or 51mm long x 16mm diameter
(5" or 2" x 0.63")
Housing material: SS316
Cable: 3m or 0.9m long (10’ or 3’)
Cable Operating Temp:
-40º to 125ºC (-40º to 257ºF)

iP-PC iP-SC iP-SC

Optional Caps available for
Industrial Probes



Choose between 2" or 5" probe


Meter Specifications
NMRR: 60dB
CMRR: 120 dB
Warm-up to rated accuracy: 30 min.
A/D Conversion: 12 bit RH and 14 bit Temperature
Reading Rate: 2 samples per second max.
Digital Filter: Programmable
Decimal Selection: None, 0.1 for temperature and humidity

Control
Action: Reverse (heat) or direct (cool)
Modes: Time and Amplitude Proportional Control Modes; selectable Manual or Auto PID, Proportional, Proportional with Integral, Proportional with Derivative with Anti-reset Windup and ON/OFF
Rate: 0 to 399.9 seconds
Reset: 0 to 3999 seconds
Cycle Time: 1 to 199 seconds; set to 0 for ON/OFF operation
Gain: 0.5 to 100% of span; Setpoints 1 or 2
Damping: 0000 to 0008
Soak: 00.00 to 99.59 (HH:MM), or OFF
Ramp to Setpoint: 00.00 to 99.59 (HH:MM), or OFF
Auto Tune: Operator initiated from front panel for one input at a time only

Control Output 1 & 2
Relay: 250Vac or 30Vdc @ 3A (resistive load); configurable for on/off, PID, Ramp and Soak
Output 1: SPDT type, can be configured as Alarm 1 output.
Output 2: SPDT type, can be configured as Alarm 2 output
SSR: 20 to 265Vac @ 0.05 - 0.5A (resistive load); continuous
DC Pulse: Non-Isolated; 10 Vdc @ 20 mA
Analog Output (Output 1 only): Non-Isolated, Proportional 0 to 10Vdc or 0 to 20mA; 500ohm max

Alarm 1 & 2 (programmable)
Type: Same as Output 1 and 2
Operation: High/low, above/below, band, latch/unlatch, normally open/normally closed and process/deviation; front panel configurations
Analog Output (programmable): Non-Isolated, Retransmission 0 to 10Vdc or 0 to 20mA, 500ohm max (Output 1 only). Accuracy is ± 1% of FS when following conditions are satisfied.
1) Input is not scaled below 1% of Input FS.
2) Analog Out is not scaled below 3% of Output FS.

Network and Serial Communications (options -C24, -C4EI, -EI)
Ethernet: Standards Compliance IEEE 802.3 10Base-T
Supported Protocols: TCP/IP, ARP, HTTPGET
RS-232/RS-422/RS-485: selectable from menu; both ASCII and Modbus protocol selectable from menu. Programmable 300 to 19.2 K baud; complete programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status
RS-485: Addressable from 0 to 199
Connection: Screw terminals

Power
Line Voltage/Power:
90 to 240 Vac ±10%, 50-400 Hz*, 110 to 375 Vdc, equivalent voltage
* No CE compliance above 60 Hz
Low Voltage/Power Option: 24 Vac** ±10%, 12 to 36 Vdc, from qualified safety approved source
**Units can be powered safely with 24Vac power, but no certification for CE/UL are claimed

Insulation
Power to Input/Output:
2500 Vac per 1 minute test
For Low Voltage/Power Option: 1500 Vac per 1 minute test
Power to Relay/SSR Outputs: 2500 Vac per 1 minute test
Relay/SSR to Relay/SSR Outputs: 2500 Vac per 1 minute test
RS-232/485 to Inputs/Outputs: 500 Vac per 1 minute test

Dimensions
i/8 Series:
48 H x 96 W x 127 mm D (1.89 x 3.78 x 5")
i/16 Series: 48 H x 48 W x 127 mm D (1.89 x 1.89 x 5")
i/32 Series: 25.4 H x 48 W x 127 mm D (1.0 x 1.89 x 5")

Panel Cutout
i/8 Series:
45 H x 92 mm W (1.772" x 3.622"), 1/8 DIN
i/16 Series: 45 mm (1.772") square, 1/16 DIN
i/32 Series: 22.5 H x 45 mm W (0.886" x 1.772"), 1/32 DIN

Weight
i/8 Series:
295 g (0.65 lb)
i/16 Series: 159 g (0.35 lb)
i/32 Series: 127 g (0.28 lb)

Display Sizes
4-digit, 9-segment LED red, green and amber programmable colors
10.2 mm (0.40") & 21 mm (0.83"): i8DH
10.2 mm (0.40"): i32, i16D, i8DV

General
Environmental Conditions: 0 to 50°C (32 to 122°F), 90% RH non-condensing: i8DV, i8DH, i16D;
0 to 55°C (32 to 131°F) 90% RH non-condensing: i32.
Measurement Category: I per EN61010-1
Double Insulation: per EN61010-1
Pollution Degree: 2 per EN61010-1
Protection: NEMA-4X (IP65) front bezel i32, i16D; NEMA-1 front bezel i8DH, i8DV
Approvals: UL & C-UL; CE per EN61010- 1:2001



To Order (Specify Model Number, see variations below in partnumber builder table)    
 Part Number   Availability   Price    Description    Qty.
 iTH-i8DH00-5 in-stock    $390.00     iTH Humidity + Temperature Controller, 1/8 DIN Dual Display Horizontal, Monitor version (no outputs), 5" probe with 10 ft cable  
 iTH-i8DV22-5 in-stock    $490.00     iTH Humidity + Temperature Controller, 1/8 DIN Dual Display Vertical, two solid state relays, 5" probe with 10 ft cable  
 iTH-i16D33-5 in-stock    $490.00     iTH Humidity + Temperature Controller, 1/16 DIN Dual Display, two form C SPDT relays, 5" probe with 10 ft cable  
 iTH-i3200-5 in-stock    $390.00     iTH Humidity + Temperature Controller, 1/32 DIN Single Display, Monitor Version (no outputs), 5" probe with 10 ft cable  
 
All dollar amounts on this site are shown in US currency.

 Part Number Builder
(1) (2) (3) (4) (5)
iTH
Option Descriptions
(1) Size
  Select
-i8DH for 1/8 DIN Dual Display Horizontal
-i8DV for 1/8 DIN Dual Display Vertical
-i16D for 1/16 DIN Dual Display
-i32 for 1/32 DIN Single Display
(2) Control Outputs
  Select
00 for Monitor version, No Outputs
22 for Two Solid State Relays
23 for One Solid State Relay and Form C SPDT
24 for 1 SSR and Pulse 10V dc
33 for 2 Relays - Form C SPDT
42 for Pulsed 10 V dc and SSR Relay
43 for Pulsed 10 V dc and Form C Relay
44 for 2 Pulsed 10 V dc
52 for Analog Output and SSR
53 for Analog output and Relay
54 for Analog output and pulse
(3) RH/Temp Probe
  Select
-2 for 2" Probe with 3ft cable
-5 for 5" probe with 10ft cable
(4) Network Options
  Select
Nothing(leave field blank) for no Network Option
-C24 for Isolated RS-232 and RS-485
-C4EI for Ethernet with Embedded Web Server + Isolated RS-485/422
-EI for Ethernet with Embedded Web Server
(5) Power Supply
  Select
Nothing(leave field blank) for for Standard power input 90-240Vac
-DC for Low Power option 12-36Vdc/24Vac
 NOTE: All combinations may not be valid, check spec sheet for valid part numbers.


   

   Back to top

Sitemap | Order Status | Careers | About Us | ISO 9001 | Worldwide Affiliates
Copyright ©2008, NEWPORT Electronics, Inc. All rights reserved.