INDUSTRIAL
pH CONTROLLERS / RECORDERS
|
The PHR-212 Series of pH recorders and controllers provides
a reliable method of monitoring, controlling and recording pH
levels of various industrial and chemical processes. Featuring
an extensive list of standard features, the PHR-212 series includes
a digital display, digital switches for alarms setpoints, remote
mount pH 4 to 20 mA transmitter, 6 amp solid state relays, front
panel adjustable dead band pots and NEMA 4X enclosure.
The controllers standard features include a digital display capable
of displaying pH readings between 2 and 12 pH, adjustable dual
alarm setpoints, dead band adjustments from 1 to 50% of setpoint,
programmable time safety delay which activates when pH correction
time is excessive and a stand by switch that disables the controller
functions during calibration.
The recorder utilizes inkless pressure sensitive recording paper
for 30 days of recording and front panel mounted calibration adjustments.
PHR-212 pH recorder includes a digital display, enclosed
in a NEMA 4X enclosure and accepts pH electrodes directly. Supplied
with one 30-day roll of recorder paper. PHC-212 is a basic
pH controller, it includes a NEMA 4X enclosure, digital display,
two setpoints for high and low alarm, adjustable dead band, two
6 amp SSR. Accepts one pH electrode input through supplied pH
transmitter.
PRC-212 pH recorder and pH controller combines the features
of the PHR-212 and PHC-212 into one compact unit. It accepts one
electrode through the transmitter that drives the recorder, controller
and digital display. Supplied with the PRC-212 is one 30-day roll
of recorder paper. PRCD-212 pH recorder/controller uses
two independent pH probes in a wall mounted NEMA 4X enclosure.
Each pH electrode performs a separate function. The electrode
input from the supplied pH transmitter drives the digital display
and controller the second pH electrode drives the recorder directly.
The recorder electrode may be placed downstream from the control
point to record the adjusted values. Supplied with the PRCD-212 is one 30-day roll of recorder paper.
 |
PRCD-212
is supplied complete with rugged NEMA-4X case,
pH transmitter and pocket thermometer.
Electrodes purchased separately. |
PHCD-212 is
a versatile dual pH controller. The PHCD-212 accepts two separate
electrode inputs and can adjust pH at two separate locations.
The dual pH model is supplied with two 4 to 20 mA pH transmitters.
When one of the two controllers is configured with the optional
ORP controller, it may be used for cyanide destruction or chrome
reduction.
PRCD-212
FAMILY

|
SPECIFICATIONS
pH Recorder
Display: None
Range: 2 to 12 (0 to 14 pH available, consult Sales)
Resolution: 0.2 pH/lateral chart deviation
Accuracy: ±0.2 pH
Repeatability: ±0.2 pH
Temperature Compensation: Manual supplied with 1093 ohm
resistor; Automatic 1000 ohm platinum RTD
Power Requirements: 120 Vac 50/60 Hz
pH Controller
Display: 12.7 mm (0.5"), 3 1/2 digit LCD
Range: 2 to 12 pH (0 to 14 pH available, consult Sales)
Resolution: 0.01 pH
Accuracy: ±0.02 pH
Repeatability: ±0.02 pH
Temperature Compensation: Manual supplied with 1093 ohm
resistor; Automatic 1000 ohm platinum RTD
Power Requirements: 120 Vac 50/60 Hz (230 Vac Optional)
Contact: Two, 6 amp SSR, requires 200 mA minimum load
Dead Band Adjustment: 0 to 50 % of setpoint
Safety Time Delay: Adjustable, 1 to 11 minutes
Time Delay Relay: 6 amp SPDT
Temperature: K-79-7 six in. stem pocket thermometer range
-10 to 110ºC
Optional ORP Controller
Display: 12.7 mm (0.5"), 3 1/2 digit LCD
Range: 0 to 1000 mV
Resolution: 1 mV
Accuracy: ±1 mV
Repeatability: ±1 mV
Power Requirements: 120 Vac 50/60 Hz
Contact: Two, 6 amp SSR, requires 200 mA minimum load
Dead Band Adjustment: 0 to 50 % of setpoint
Safety Time Delay: Adjustable, 1 to 11 minutes
Time Delay Relay: 6 amp SPST; 0 to 14 pH available, consult
Sales
|
|
|
|
† All dollar amounts on this site are shown in US currency.
Note: Each unit comes complete with operator's manual, NEMA 4X enclosure, appropriate number of pH transmitter(s), K-79 pocket thermometer. Models that include a pH recorder also supplied with one roll of 30-day chart paper.
To order 230 Vac power input, suffix part number “-230VAC” to part number and add $50 to the price.
Ordering Example: (1) PRCD-212 dual input pH controller/recorder = $2850
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
Part Number Builder |
 |
 |
 |
 |
 |
 |
|
|
|
Option Descriptions
|
|
(1)
|
Base Unit
|
| |
Select PHR for pH recorder and monitor PHC for single input pH controller PRC for single input pH controller/recorder PRCD for dual input pH controller/recorder PHCD for dual input pH controller
|
(2)
|
Range
|
| |
Select 212 for 2 to 12 pH 014 for 0 to 14 pH ORP for ORP - 0 to 1000 mV range (controller only)
|
| NOTE: All combinations may not be valid, check spec sheet for valid part numbers. |
|
|
 |
 |
|
|
|
|