3 1/2 DIGIT PROCESS RECEIVER, TRANSMITTER & CONTROLLER
Q2000P Process Receiver
Q2000E Process Receiver with Excitation Output
Electromagnetic Compatibility

NEWPORT PRODUCT INFO
MANUAL - PDF Version Q2000P
MANUAL - PDF Version Q2000E
MECHANICAL 1/8 DIN (1A) Case
MECHANICAL Connections Diagram
PRICE
REQUIRES ADOBE ACROBAT - HELP
QUANTA STANDARD FEATURES
10 or 15 V dc excitation output (Q2000E)
±1,999-count display span
Selectable current ranges from ±1 to ±50 mA
Selectable voltage ranges from ±0.5 to ±20 V
Built-in shunts and attenuators
Zero adjustment to ±100% of readout
Standard signal ranges of 4-20 mA, 10-50 mA, 1-5 V or 0-10 V
Front-panel accessible fine-zero and fine-span adjustments
1 mV/count analog output
LED or LCD display
Automatic polarity
Display hold and test
120/240 V ac, 5 V dc, 9-32 V dc or 26-56 V dc power
Screw-terminal barrier strip
1/8 DIN case
OPTIONS
Analog output for user-selected span
Single-setpoint 10 A relay control
Dual-setpoint 10 A relay control
Proportional 4-20 mA control
Time-proportional 2 A solid-state relay control
Parallel BCD output, isolated
NEMA-4 splash-proof lens cover

The Q2000P is a 3 1/2 digit process receiver with extensive zero and span adjustment capability for readout in engineering units. The more popular process signals are 4-20 mA, 10-50 mA, 1-5 V and 0-10 V. The Q2000P can also be scaled for other signal levels. Full-scale input ranges are selectable from ±1 to ±50 mA (current signal) or ±0.5 to ±20 V (voltage signal). Zero is adjustable up to ±100% of full-scale readout for every input range.

The Q2000E is an enhanced version of the Q2000P with an excitation output for powering transmitters and active transducers. In many cases, this output can eliminate the need for a more expensive external supply. The output shares the ground of the signal input. Two output levels are jumper-selectable: 10 V dc at up to 50 mA and 15 V dc at up to 25mA.

CONFIGURATION AND CALIBRATION
The price of the Q2000P and Q2000E includes configuration and calibration, normally provided by an authorized Newport distributor. Both models can also be configured and scaled in the field. Full-scale signal, coarse-span and coarse-zero ranges are selected by plug-in jumpers. A complete set of internal shunts and attenuators are already on board. Fine-zero and fine-span potentiometers are accessible behind the lens to allow final calibration or field recalibration without removal of the panel meter.

POWER AND DISPLAY OPTIONS
Six types of meter power are available: 120 V ac, 240 V ac, 24 V ac, 5 V dc, isolated 9-32 V dc and isolated 26-56 V dc. An LED display is standard. An LCD display is avail- able and is useful for viewing in bright ambient light.

ANALOG OUTPUT OPTIONS
A 1 mV/count (±2 V full-scale) analog output is standard and is ideal for driving a strip-chart recorder. An additional analog output can be provided by an optional vertical plug-in board. Available output signals are 0-5 V dc, 0-10 V dc, 0-1 mA (source or sink), and 4-20 mA (source or sink). The top and bottom of each output range can be scaled to fit a user-selected display span.

CONTROL OUTPUT OPTIONS
Additional outputs can be provided by a horizontal upper board. Available options include single-setpoint control with one 10 A relay, dual-setpoint control with two 10 A relays, 4-20 mA proportional control (source or sink), time-proportional 2 A solid-state relay control, and isolated, parallel BCD output. For additional information, please refer to the QUANTA and Mechanical sections.


SPECIFICATIONS

ANALOG INPUT
VOLTAGE RECEIVER
Most-sensitive scaling
Least-sensitive scaling
Signal range
±0.5 V
±20 V
Display range
±1,999 counts
±1,999 counts
Resolution
250 µV/count
10 mV/count
Input resistance
100 kohm
1.0 Mohm
Bias current
100 pA
13 pA
Maximum voltage
250 Vp
250 Vp

CURRENT RECEIVER
Most-sensitive scaling
Least-sensitive scaling
Signal range
±1.0 mA
±50.0 mA
Display range
±1,999 counts
±1,999 counts
Resolution
500 nA/count
25µA/count
Input resistance
500 ohm
10 ohm
Voltage drop, max
±0.5 V
±0.5 V

VOLTAGE & CURRENT RECEIVER
Full-scale signal input: Six jumper-selectable ranges
Coarse-span adjustment: Four jumper-selectable ranges
Fine-span adjustment: Front-panel potentiometer
Coarse-zero adjustment: Four jumper-selectable ranges
Fine-zero adjustment: Front-panel potentiometer
Input configuration: Single-ended

NOISE REJECTION
NMR, SIG HI to SIG LO: 75 dB, 50/60 Hz
CMR, SIG GND to PWR GND: 120 dB
CMV, SIG GND to PWR GND: 1500 Vp per HV test, 354 Vp per IEC spacing

ACCURACY AT 25°C
Error, max:
±0.05% of reading ±1 count
Span tempco: ±0.01% of reading/°C
Zero drift, max: ±0.01% of reading/°C
Offset drift, max: ±(0.01% offset V ±0.01% FS V)/°C
Step response: 1 s to 99.9% of span
Warmup to rated accuracy: 10 min

ANALOG-TO-DIGITAL CONVERSION
Technique: Dual-slope, average-value
Signal integration period: 100 ms
Read rate: 2.5/s

TRANSMITTER EXCITATION SUPPLY (Q2000E)
Output voltage:
10 or 15 V dc, jumper-selectable
Output current, max: 50 mA at 10 V dc, 25 mA at 15 V dc, 50 mA for sum for all output currents, including control output and analog output
Line regulation, max: ±0.2% for 10% change of AC line power voltage
Load regulation, max: ±0.5% from zero to max load
Ripple at 50/60 Hz: ±0.01%

DISPLAY
LED: 0.56 in (14.2 mm) 7-segment, red
LCD: 0.50 in (12.7 mm) 7-segment liquid crystal
Symbols: ­1.8.8.8
Decimal point positions: Three positions selectable by jumpers behind lens or at connector
Overrange indication: Three-least significant digits blanked

POWER
AC voltages:
120, 240 or 24 V ac +10%/­15%
AC frequency: 49-440 Hz
DC voltages: 9-32 V dc, isolated to 300 Vp; 26-56 V dc, isolated to 300 Vp; 5 V dc ±5%, non-isolated
Power consumption: 10 W max

ENVIRONMENTAL
Operating temperature:
0 to 60°C
Storage temperature: ­40 to +85°C
Relative humidity: 95% at 40°C (non-condensing)

MECHANICAL
Dimensions: Newport DIN1A (1/8 DIN) case (see Mechanical section for drawings)
Weight: 17 oz (480 g)
Case material: 94V-0 UL-rated polycarbonate



To Order (Specify Model Number, see variations below in partnumber builder table)    
 Part Number   Availability   Price    Description    Qty.
 Q2000-P in-stock    $285.00     Quanta meter,3-1/2 digit display, red LED display, 120 Vac power, 1 mV per count analog output, scalable process signal input (from ±0.5 to ±20 Vdc or ±1 to ±50 mA) (no control output)  
 Q2060-P in-stock    $420.00     Quanta meter,3-1/2 digit display, red LED display, 120 Vac power, isolated 4 to 20 mA analog output, scalable process signal input (from ±0.5 to ±20 Vdc or ±1 to ±50 mA) (no control output)  
 Q2005-P in-stock    $410.00     Quanta meter,3-1/2 digit display, red LED display, 120 Vac power, 1 mV per count analog output, single setpoint 10 A relay, scalable process signal input (from ±0.5 to ±20 Vdc or ±1 to ±50 mA)  
 
All dollar amounts on this site are shown in US currency.

 Part Number Builder
(1) (2) (3) (4) (5) (6) (7)
Q -
Option Descriptions
(1) Display Resolution and Case Style
  Select
2 for ±1,999 counts (3 1/2 digits)
3 for ±1,999 with INFINITY FAMILY BEZEL AND ADAPTER
9 for ±9,999 counts (4 digits)
8 for ±9,999 with INFINITY FAMILY BEZEL AND ADAPTER
(2) Display Type & Meter Power - LCD
  Select
0 for LED, 120 Vac (49/440 Hz) (BQ20 or BQ90)
1 for LCD, 120 Vac (49/440 Hz) (BQ21)
2 for LED, 240 Vac (49/440 Hz) (BQ22 or BQ92)
3 for LCD, 240 Vac (49/440 Hz) (BQ23)
4 for LED, 9-32 Vdc (isolated) (BQ24 or BQ94)
5 for LCD, 9-32 Vdc (isolated) (BQ25)
6 for LED, 5 Vdc** (BQ26 or BQ96)
7 for LCD, 5 Vdc** (BQ27)
8 for LED, 24 Vac (BQ28 or BQ98)
9 for LCD, 24 Vac (BQ29)
A for LED, 26-56 Vdc (isolated) (BQ2A or BQ9A)
B for LCD, 26-56 Vdc (isolated) (BQ2B)
(3) Analog Output Adders
  Select
0 for ±1 or ±2 V recorder output, non-isolated. (standard)
1 for 0-5 Vdc, non-isolated (BA01)
2 for 0-10 Vdc, non-isolated (BA01)
3 for 0-1 mA, source or sink, non-isolated (BA01)
4 for 4-20 mA, source or sink, non-isolated (BA01)
5 for 4-20 mA, sink (high-compliance), non-isolated. (BA02)
6 for 4-20 mA, ISOLATED (BA03)
(4) Control Output Adders
  Select
0 for None
1 for Dual-setpoint 10 A relay. (BDT1)
2 for Proportional 4-20 mA control, source or sink (BDP1)
3 for Time-proportional solid-state 2 A relay plus proportional 4-20 mA control, source or sink. (BDP2)
4 for BCD (isolated, latched, buffered, byte addressable). Includes 50-pin mass-termination connector. (BDD2)
5 for Single-setpoint 10 A relay (BDS1)
(5) Signal Conditioning Input Adders
  Select
P for Process Signal Input
E for Process Signal Input plus Excitation Output
(6) Display Color
  Select
Nothing(leave field blank) for Red Display (standard)
,G for Green Display
(7) Lens
  Select
Nothing(leave field blank) for Standard Lens (with Newport logo)
,BL for Blank Lens
 NOTE: All combinations may not be valid, check spec sheet for valid part numbers.


   

   Back to top

Sitemap | Order Status | Careers | About Us | ISO 9001 | Worldwide Affiliates | Terms & Conditions
Copyright ©2012, NEWPORT Electronics, Inc. All rights reserved.