SPECIFICATIONS
1,999 or 9,999-Count Display Span
100 mV to 650 V Ranges
2 µA to 1 A Ranges
Special Scaling for 5 A Current Transformer
0.1 mV/Count Analog Output
Front-Panel Accessible Span Adjustment
Bright, 0.56" (14.2 mm) LED Display
Display Hold and Test
120/240 Vac, 9-32 Vdc Power
Screw-Terminal Barrier Strip
1/8 DIN Case
OPTIONS
Analog Output for User-Selected Span
Single-Setpoint 10 A Relay Control
Dual-Setpoint 10 A Relay Control
Parallel BCD Output, Isolated

The QUANTA® AC AVG voltmeter and ammeter use a precision op-amp rectifier circuit to provide an economical AC-average meter, which is calibrated to display the true-RMS value of sinusoidal signals. The QUANTA AC RMS voltmeter and ammeter use an integrated circuit that computes the true-root-mean-square value of complex waveforms. Screw-terminals are provided for AC or DC coupling. AC coupling allows the measurement of the AC component or ripple from a signal with both AC and DC components. DC coupling allows the measurement of true-RMS, including both DC and AC components.

The signal conditioner provides six current ranges, as determined by an internal shunt resistor. In addition, there is a special 5 A range, which allows direct connection to a current transformer (CT) with 5 A secondary, without need for a stepdown transformer. Proper scaling is obtained for primary currents of 10, 100 and 1000 A.

SPECIFICATIONS


ANALOG INPUT, Q2000C & Q2000F / Q3000C & Q3000F
Range
-
199.9 mV
1.999 V
Resolution
-
100 µV
1 mV
Maximum input
-
50 Vp
100 Vp
Input resistance
-
1.1 Mohm
1.1 Mohm

Range
19.99 V
199.9 V
650 V
Resolution
10 mV
100 mV
1 V
Maximum input
250 Vp
500 Vp
920 Vp
Input resistance
1.0 Mohm
1.0 Mohm
10 Mohm

ANALOG INPUT, Q2000D & Q2000G / Q3000D & Q3000G
Range
19.99 µA
199.9 µA
1.999 mA
Resolution
10 nA
100 nA
1 µA
Maximum input
3 mA
10 mA
30 mA
Input resistance
10 kohm
1 kohm
100ohm

Range
19.99 mA
199.9 mA
1.999 A
Resolution
10 µA
100 µA
1 mA
Maximum input
100 mA
500 mA
2.2 A
Input resistance
10 ohm
1 ohm
0.1 ohm

Range
19.99 A
199.9 A
1999 A
Resolution
10 mA
100 mA
1 A
Maximum input
5 A CT
5 A CT
5 A CT
Input resistance
0.01ohm
0.01ohm
0.01ohm

ANALOG INPUT, Q9000C & Q9000F / Q8000C & Q8000F
Range
99.99 mV
999.9 mV
Resolution
10 µV
100 µV
Maximum Input
50 Vp
100 Vp
Input Resistance
1.1 Mohm
1.1 Mohm

Range
9.999 V
99.99 V
650.V
Resolution
1 mV
10 mV
100 mV
Maximum Input
250 Vp
500 Vp
920 Vp
Input Resistance
1.0 Mohm
1.0 Mohm
10 Mohm

ANALOG INPUT, Q9000D & Q9000G / Q8000D & Q8000G
Range
9.999 µA
99.99 µA
999.9 µA
Resolution
1 nA
10 nA
100 nA
Maximum Input
3 mA
10 mA
30 mA
Input Resistance
10 kohm
1 kohm
100 ohm

Range
9.999 A
99.99 A
999.9 A
Resolution
1 mA
10 mA
100 mA
Maximum Input
5 A CT
5 A CT
5 A CT
Input Resistance
0.01 ohm
0.01 ohm
0.01 ohm

ACCURACY at 25°C (AC)
Maximum Error: ±0.1% of reading ±10 counts
Span tempco: ±0.01% of reading/°C (AC)
Step response: 1 s to 99.9% of span
Frequency range for rated accuracy:
147 to 1000 Hz
Warmup to rated accuracy: Less than 30 min.

ACCURACY at 25°C (RMS) (1% to 100% of full scale)

Maximum error, AC coupling:
±0.1% of reading ±10 cts, 47 Hz to 5 kHz
Maximum error, DC coupling: ±0.1% of reading ±10 cts, 9 Hz to 5 kH
Span tempco: ±0.03% of reading/°C (typ)
Zero tempco: 0.15 mV/°C (typ)
Step response: 1 sec to 99.9% of span
Warmup to rated accuracy: Less than 30 min.

CONVERSION
Technique:
Dual-slope, average-value
Signal integration period: 100 ms
Read rate: 2.5/sz


Range Code
Input Range
Range Code True RMS Q2000 / Q3000 Q9000 / Q8000
CVR2
FVR2
199.99 mV
99.99 mV
CVR3
FVR3
1.999 V
999.9 mV
CVR4
FVR4
19.99 V
9.999 V
CVR5
FVR5
199.9 V
99.99 V
CVR6
FVR6
650 V
650.0 V
DCR1
GCR1
19.99 µA
9.999 µA
DCR2
GCR2
199.9 µA
99.99 µA
DCR3
GCR3
1.999 mA
999.9 µA
DCR4
GCR4
19.99 mA
9.999 mA
DCR5
GCR5
199.99 mA
99.99 mA
DCR6
GCR6
1.999 A
999.9 mA
DCR7
GCR7
5 A CT
5 A CT


To Order (Specify Model Number, see variations below in partnumber builder table)    
 Part Number   Availability   Price    Description    Qty.
 Q2000-CVR2 in-stock    $290.00     Quanta meter,3-1/2 digit display, red LED display, 120 Vac power, 1 mV per count analog output, AC AVG voltage input with 199.9 mV input range (no control output)  
 Q9000-DCR6 1 Week    $330.00     Quanta meter,4 digit display, red LED display, 120 Vac power, 1 mV per count analog output, AC AVG current input with 999.9 mA input range (no control output)  
 Q2020-FVR6 in-stock    $395.00     Quanta meter,3-1/2 digit display, red LED display, 120 Vac power, 0 to 10 Vdc analog output, AC RMS voltage input with 650.0 V input range (no control output)  
 Q9000-GCR5 1 Week    $365.00     Quanta meter,4 digit display, red LED display, 120 Vac power, 1 mV per count analog output, AC RMS current input with 99.99 mA input range (no control output)  
 
All dollar amounts on this site are shown in US currency.

 Part Number Builder
(1) (2) (3) (4) (5) (6) (7)
Q -
Option Descriptions
(1) Display Resolution and Case Style
  Select
2 for ±1,999 counts (3 1/2 digits)
3 for ±1,999 with INFINITY FAMILY BEZEL AND ADAPTER
9 for ±9,999 counts (4 digits)
8 for ±9,999 with INFINITY FAMILY BEZEL AND ADAPTER
(2) Display Type & Meter Power - LCD
  Select
0 for LED, 120 Vac (49/440 Hz) (BQ20 or BQ90)
1 for LCD, 120 Vac (49/440 Hz) (BQ21)
2 for LED, 240 Vac (49/440 Hz) (BQ22 or BQ92)
3 for LCD, 240 Vac (49/440 Hz) (BQ23)
4 for LED, 9-32 Vdc (isolated) (BQ24 or BQ94)
5 for LCD, 9-32 Vdc (isolated) (BQ25)
6 for LED, 5 Vdc** (BQ26 or BQ96)
7 for LCD, 5 Vdc** (BQ27)
8 for LED, 24 Vac (BQ28 or BQ98)
9 for LCD, 24 Vac (BQ29)
A for LED, 26-56 Vdc (isolated) (BQ2A or BQ9A)
B for LCD, 26-56 Vdc (isolated) (BQ2B)
(3) Analog Output Adders
  Select
0 for ±1 or ±2 V recorder output, non-isolated. (standard)
1 for 0-5 Vdc, non-isolated (BA01)
2 for 0-10 Vdc, non-isolated (BA01)
3 for 0-1 mA, source or sink, non-isolated (BA01)
4 for 4-20 mA, source or sink, non-isolated (BA01)
5 for 4-20 mA, sink (high-compliance), non-isolated. (BA02)
6 for 4-20 mA, ISOLATED (BA03)
(4) Control Output Adders
  Select
0 for None
1 for Dual-setpoint 10 A relay. (BDT1)
2 for Proportional 4-20 mA control, source or sink (BDP1)
3 for Time-proportional solid-state 2 A relay plus proportional 4-20 mA control, source or sink. (BDP2)
4 for BCD (isolated, latched, buffered, byte addressable). Includes 50-pin mass-termination connector. (BDD2)
5 for Single-setpoint 10 A relay (BDS1)
(5) Signal Conditioning Input Adders
  Select
CVR2 for AC AVG Voltage 199.9 mV (Q2000/Q3000) or 99.99 mV (Q8000/Q9000)
CVR3 for AC AVG Voltage 1.999 V (Q2000/Q3000) or 999.9 mV (Q8000/Q9000)
CVR4 for AC AVG Voltage 19.99 V (Q2000/Q3000) or 9.999 V (Q8000/Q9000)
CVR5 for AC AVG Voltage 199.9 V (Q2000/Q3000) or 99.99 V (Q8000/Q9000)
CVR6 for AC AVG Voltage 650 V (Q2000/Q3000) or 650.0 V (Q8000/Q9000)
DCR1 for AC AVG Current 19.99 µA (Q2000/Q3000) or 9.999 µA (Q8000/Q9000)
DCR2 for AC AVG Current 199.9 µA (Q2000/Q3000) or 99.99 µA (Q8000/Q9000)
DCR3 for AC AVG Current 1.999 mA (Q2000/Q3000) or 999.9 µA (Q8000/Q9000)
DCR4 for AC AVG Current 19.99 mA (Q2000/Q3000) or 9.999 mA (Q8000/Q9000)
DCR5 for AC AVG Current 199.9 mA (Q2000/Q3000) or 99.99 mA (Q8000/Q9000)
DCR6 for AC AVG Current 1.999 A (Q2000/Q3000) or 999.9 mA (Q8000/Q9000)
DCR7 for 5 Amp Current transformer- 5 A = 199.9 A (Q2000/Q3000) or 5 A = 99.99 A (Q8000/Q9000)
FVR2 for True-RMS Voltage 199.9 mV (Q2000/Q3000) or 99.99 mV (Q8000/Q9000)
FVR3 for True-RMS Voltage 1.999 V (Q2000/Q3000) or 999.9 mV (Q8000/Q9000)
FVR4 for True-RMS Voltage 19.99 V (Q2000/Q3000) or 9.999 V (Q8000/Q9000)
FVR5 for True-RMS Voltage 199.9 V (Q2000/Q3000) or 99.99 V (Q8000/Q9000)
FVR6 for True-RMS Voltage 650 V (Q2000/Q3000) or 650 V (Q8000/Q9000)
GCR1 for True-RMS Current 19.99 µA (Q2000/Q3000) or 9.999 µA (Q8000/Q9000)
GCR2 for True-RMS Current 199.9 µA (Q2000/Q3000) or 99.99 µA (Q8000/Q9000)
GCR3 for True-RMS Current 1.999 mA (Q2000/Q3000) or 999.9 µA (Q8000/Q9000)
GCR4 for True-RMS Current 19.99 mA (Q2000/Q3000) or 9.999 mA (Q8000/Q9000)
GCR5 for True-RMS Current 199.9 mA (Q2000/Q3000) or 99.99 mA (Q8000/Q9000)
GCR6 for True-RMS Current 1.999 A (Q2000/Q3000) or 999.9 mA (Q8000/Q9000)
GCR7 for 5 Amp Current transformer 5 A = 199.9 A (Q2000/Q3000) or Default calibration 5 A=99.99 A (Q8000/Q9000)
(6) Display Color
  Select
Nothing(leave field blank) for Red Display (standard)
,G for Green Display
(7) Lens
  Select
Nothing(leave field blank) for Standard Lens (with Newport logo)
,BL for Blank Lens
 NOTE: All combinations may not be valid, check spec sheet for valid part numbers.


   
Keywords: AC VOLTMETER, AMMETER & CONTROLLER AVG RMS

   Back to top

Sitemap | Order Status | Careers | About Us | ISO 9001 | Worldwide Affiliates | Terms & Conditions
Copyright ©2012, NEWPORT Electronics, Inc. All rights reserved.