4-DIGIT
THERMOCOUPLE METERS, TRANSMITTERS & CONTROLLERS
MODEL Q9000J / Q9000K / Q9000T
QUANTA
Models Q9000J, Q9000K and Q9000T
are 4-digit indicator/controllers for thermocouple types J, K
and T, respectively. They are complete with linearization, cold-junction
compensation, and sensor-break detection. Readout is in °C
or °F with 0.1° resolution, as selected by push-on jumpers.
What makes QUANTA exceptional is the wide choice of options.
POWER OPTIONS
Six types of meter power are available: 120 Vac, 240 Vac,
24 Vac, 5 Vdc, isolated 9-32 Vdc, or isolated 26-56 Vdc.
ANALOG OUTPUT
OPTIONS
A
0.1 mV/count (±2 V full-scale) analog output is standard
and is useful for driving a strip-chart recorder. An additional
analog output can be provided by an optional vertical plug-in
board. Available output signals are 0-5 Vdc, 0-10 Vdc, 0-1 mA
(source or sink), and 4-20 mA (source or sink). The top and bottom
of each output range can be scaled to fit a user-selected display
span.
CONTROL OUTPUT OPTIONS
Additional outputs can be provided by a horizontal upper board.
Available options include single-setpoint control with one 10
A relay, dual-setpoint control with two 10 A relays, 4-20 mA proportional
control (source or sink), time-proportional 2 A solid-state relay
control, and isolated, parallel BCD output. For additional information,
please refer to the QUANTA Options, and Mechanical sections.
SPECIFICATIONS
ANALOG
INPUT
TC
types: J (Iron-Constantan), K (Chromel-Alumel), T (Copper-Constantan)
Calibration:
To IPTS-68, as published in NIST monograph 125 (March 1974), ASTM
E130-72 or ASA C96.2-1973
Configuration: Single-ended (-TC lead connected to ANA
GND)
Input resistance: 100 Mohm
Sensor-break detection: 400 nA current source
Max lead resistance for rated accuracy: 500ohm (type J
ohm), 395ohm (type K ohm), 200ohm (type T ohm)
Zero tempco (cold-junction error): ±0.06 deg/deg
Span tempco, 10°C to 40°C: ±0.01% of reading/°C
NOISE REJECTION
NMR: 125dB at 50/60 Hz
Overvoltage protection: 120 V rms (continuous), 240 V rms
(30 s max)
CMR: 120 dB with 250 ohm imbalance
CMV: 1500 Vp per HV test, 354 Vp per IEC spacing
ANALOG-TO-DIGITAL CONVERSION
Input configuration: Single-ended SIG HI (TC + ) lead connected
to SIG GND through 10ohm
Technique: Dual-slope, average-value
Polarity: Automatic
Signal integration period: 100 ms
Read rate: 2.5/s
DISPLAY
Type: 7-segment, red LED
Height: 0.56 in (14.2 mm)
Symbols: 8.8.8.8
Decimal point positions: Three positions selectable by
jumpers behind lens or at connector
0 to 9,999 counts: Normal operation
10,000 to 19,999 counts: Four least-significant digits
flash reading
Beyond 19,999 counts: All four digits flash zeros
Sensor-break indication: Three least-significant digits
blanked
POWER
AC voltages: 120, 240, 100 or 24 Vac +10%/15%
AC frequency: 49-63 Hz
DC voltages: 9-32 Vdc, isolated to 300 Vp; 26-56 Vdc, isolated
to 300 Vp; 5 V dc ±5%, non-isolated
Power consumption: 10 W max
ENVIRONMENTAL
Operating temperature: 0 to 60°C
Storage temperature: 40 to +85°C
Relative humidity: 95% at 40°C (non-condensing)
MECHANICAL
Dimensions: Newport DIN1A (1/8 DIN) case (see Mechanical
section for drawings)
Weight: 17 oz (480 g)
Case material: 94V-0 UL-rated polycarbonate
|
|
|
|
† All dollar amounts on this site are shown in US currency.
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
Part Number Builder |
 |
 |
 |
 |
 |
 |
|
|
|
Option Descriptions
|
|
(1)
|
Display Resolution and Case Style
|
| |
Select 9 for ±9,999 counts (4 digits) 8 for ±9,999 with INFINITY FAMILY BEZEL AND ADAPTER
|
(2)
|
Display Type & Meter Power - LCD
|
| |
Select 0 for LED, 120 Vac (49/440 Hz) (BQ20 or BQ90) 1 for LCD, 120 Vac (49/440 Hz) (BQ21) 2 for LED, 240 Vac (49/440 Hz) (BQ22 or BQ92) 3 for LCD, 240 Vac (49/440 Hz) (BQ23) 4 for LED, 9-32 Vdc (isolated) (BQ24 or BQ94) 5 for LCD, 9-32 Vdc (isolated) (BQ25) 6 for LED, 5 Vdc** (BQ26 or BQ96) 7 for LCD, 5 Vdc** (BQ27) 8 for LED, 24 Vac (BQ28 or BQ98) 9 for LCD, 24 Vac (BQ29) A for LED, 26-56 Vdc (isolated) (BQ2A or BQ9A) B for LCD, 26-56 Vdc (isolated) (BQ2B)
|
(3)
|
Analog Output Adders
|
| |
Select 0 for ±1 or ±2 V recorder output, non-isolated. (standard) 1 for 0-5 Vdc, non-isolated (BA01) 2 for 0-10 Vdc, non-isolated (BA01) 3 for 0-1 mA, source or sink, non-isolated (BA01) 4 for 4-20 mA, source or sink, non-isolated (BA01) 5 for 4-20 mA, sink (high-compliance), non-isolated. (BA02) 6 for 4-20 mA, ISOLATED (BA03)
|
(4)
|
Control Output Adders
|
| |
Select 0 for None 1 for Dual-setpoint 10 A relay. (BDT1) 2 for Proportional 4-20 mA control, source or sink (BDP1) 3 for Time-proportional solid-state 2 A relay plus proportional 4-20 mA control, source or sink. (BDP2) 4 for BCD (isolated, latched, buffered, byte addressable). Includes 50-pin mass-termination connector. (BDD2) 5 for Single-setpoint 10 A relay (BDS1)
|
(5)
|
Signal Conditioning Input Adders
|
| |
Select JDC1 for Type J Thermocouple input -40.0 to 760.0°C (BSCJ) JDF1 for Type J Thermocouple input -40.0 to 999.9°F (BSCJ) KDC1 for Type K Thermocouple input -40.0 to 999.9°C (BSCK) KDF1 for Type K Thermocouple input -40.0 to 999.9°F (BSCK) TDC1 for Type T Thermocouple input -184.0 to 371.0°C (BSCT) TDF1 for Type T Thermocouple input -300.0 to 700.0°F (BSCT)
|
(6)
|
Display Color
|
| |
Select Nothing(leave field blank) for Red Display (standard) ,G for Green Display
|
(7)
|
Lens
|
| |
Select Nothing(leave field blank) for Standard Lens (with Newport logo) ,BL for Blank Lens
|
| NOTE: All combinations may not be valid, check spec sheet for valid part numbers. |
| | | | | |
|
 |
 |
|
|
|
|